DC LOAD BANK PDL 500-40K
- Wide input voltage range (500 ~ 10)
- High power in a small volume
- Precise constant current control with accuracy less than 0.5 A
- Separate monitor and control section from the device
- Ability to test batteries under real load
- Real-time reporting and plotting during the test
- Ability to test various batteries (Nickel-Cadmium - Lead-Acid - Lithium)
- Dynamic discharge technology - maximum current at all voltages
- Support for parallel operation to increase power capacity
Description
The PDL series DC loadbank is an advanced tool for testing, discharging, and evaluating the performance of various industrial batteries. This device, capable of operating in three operating modes CC (constant current), CP (constant power) and CR (constant resistance) and with a wide voltage range from 10 to 500 volts, is ideal for testing nickel-cadmium (Ni-Cd), lead-acid and lithium batteries. The compact design and high power density make it easy to use in space-constrained environments. Precise current control with accuracy of less than 0.5 A ensures a stable and reliable discharge. The Central Supervision Unit (CSU) monitoring and control module enables remote monitoring and system management. Test results can be viewed, saved and edited on a personal computer via the Niawell CSU Logger software provided with the device. In addition, comprehensive data logging, real-time charts and generation of PDF reports enable precise and professional analysis of battery performance. The simple user interface, quick setup and stable operation make the PDL a smart choice for industrial testing centers.
Specifications
Electrical specifications
Input voltage range
10 ~ 500
Output power
PDL 500-80K: 80 KW
PDL-500-40K: 40 KW
PDL-500-40K: 40 KW
Maximum current
PDL 500-80K: 200 A
PDL-500-40K: 110 A
PDL-500-40K: 110 A
Auxiliary input power
AC 220V, 50HZ, 6A
Cooling method
Vertical airflow by fan
Modes
Current Mode - Power Mode - Resistance Mode
Minimum load step
0.5A (Current Mode), 100W (Power Mode), 0.1Ω (Resistance Mode)
Type of power switch
Power IGBT & MOSFET
Protections
Fan failure - Thermal cut-outs - Overload protection - Emergency stop button - Reverse Polarity
Environmental conditions
Temperature range (°C)
0-50 °C for indoor use
Storage and Transportation
-40°C to +70°C (-40°F to +158°F)
Humidity
5% – 95% RH, non-condensing
Operating Altitude
3000 m (10000 ft)
General Features
Testable Items
Batteries & DC Power Supplies
Capabilities
Graphing – Centralized control remotely via network cable
Test Storage
Stores last 12 tests for review with PDF export
Items
Accessories
CSU - Power Cable with connectors - Auxiliary power supply - Network cable - Cable for log - Case for auxiliarys parts - Cover
Physical specifications
Weight
PDL 500-80K: 85 KG
PDL-500-40K: 55 KG
PDL-500-40K: 55 KG
Dimensions (W×L×H) cm
PDL 500-80K: 46×95×75
PDL-500-40K: 35×78×50
PDL-500-40K: 35×78×50